Rack power, PUE and UPS runtime calculator

How much do your servers draw, and how much does everything around them cost? Three calculations: the power, cost and heat of a set of servers, a room's PUE, and a UPS's runtime. The formulas are under the result.

The calculation runs in your browser: nothing you type is sent anywhere.

Power, consumption and heat

Your parameters

U
W

Power actually drawn, not the PSU rating.

Used to compare with the 100 to 150 W per U allowance.

W

Switches, firewalls, storage arrays…

A small room rarely gets below a PUE of 2.

€/kWh

0.25 € excl. VAT/kWh: the value from our server room or datacenter page.

Result

Yearly electricity cost

6,570 € excl. VAT

3,285 € excl. VAT for the machines, 3,285 € excl. VAT for cooling and losses

IT load

1.50 kW

i.e. 1.53 kVA (power factor 0.98)

Energy per year

26,280 kWh

of which 13,140 kWh for IT

Heat to remove

5,118 BTU/h

i.e. 1.50 kW of cooling

Matching colocation allowance

Half rack: the load fits within about 2 kVA contracted.

300 W per U on average

PUE calculation

Your parameters

kWh

Main meter: IT, cooling, lighting, losses.

kWh

Measured at the UPS output or the PDUs, over the same period.

Result

PUE

2.00

50% of the energy does not reach IT

UPS runtime

Your parameters

W
V
Ah

For example 24 V for two 12 V batteries in series.

%
%

Example values: replace them with your UPS's.

Result

Estimated runtime

31 min

156 Wh of usable energy

Linear estimate. Under heavy load, a lead-acid battery delivers less than its rated capacity (Peukert's law): real runtime is shorter. The manufacturer's runtime curves prevail.

How the calculation works

IT power is the sum of the average draws actually measured, not the power supply rating on the label. Everything else follows:

P (kW)        = servers × average W + other equipment
S (kVA)       = P / cos φ          (cos φ ≈ 0.98)
E_IT (kWh/yr) = P × 8,760 h
E_total       = E_IT × PUE
yearly cost   = E_total × price per kWh
heat          = P × 3.412 BTU/h per watt

PUE (Power Usage Effectiveness) relates the facility's total energy to the energy of the IT equipment alone. Its definition is standardised in ISO/IEC 30134-2. A PUE of 2 means one kWh of IT costs two at the meter: the second goes to air conditioning, UPS units, conversion losses and lighting. A small room rarely gets below a PUE of 2. Datacenters publish their own figure: check the period and measurement point it is based on before comparing.

UPS runtime is estimated from the usable energy of its batteries:

usable energy (Wh) = V × Ah × strings × depth of discharge × efficiency
runtime (min)      = usable energy / load (W) × 60
This is a linear estimate. A lead-acid battery discharged quickly delivers less than its rated capacity (Peukert's law), and it loses capacity as it ages, faster in a hot room. When choosing a UPS, the manufacturer's runtime curves prevail.

What the calculation says about your room

By default the calculator uses the example from our comparison server room or datacenter: five 300 W servers, 0.25 € excl. VAT per kWh, a PUE of 2. Powering the machines costs 3,285 € excl. VAT a year, and about the same again for cooling and losses, roughly 6,600 € excl. VAT a year. That figure is accurate, but it is only the visible part: the page details air conditioning servicing, UPS testing, the generator and on-call cover, which weigh more than the kWh.

The colocation allowance shown under the result follows the market practice described in that comparison: per U, pricing assumes 100 to 150 W per U; beyond 3 to 4 U, a quarter rack with about 1 kVA contracted becomes the better deal, then a half rack with about 2 kVA. Above that, contracted power decides, not the number of U. Our own racks are at Equinix, in the Paris region: the list of Equinix datacenters where we are present (fr) is published with our network.

A UPS covers a short outage, from a few minutes to half an hour depending on its sizing. It replaces neither the generator nor cooling: when air conditioning stops, the temperature rises within minutes, UPS or not. We lived through it and documented it during the cooling incident at Equinix PA4.

After the calculation

UPS runtime only matters if someone is alerted when it switches to battery, at night or at the weekend. That is the job of 24/7 IT on-call support, which also monitors temperature and redundant power supplies.

And a power outage always ends up as minutes of downtime. To see how many your service commitment allows, and what a redundant power feed gains you, go to the uptime and SLA calculator.

Frequently asked questions

How do you calculate PUE?

Divide the total energy used by the facility by the energy used by the IT equipment alone, over the same period. A room drawing 26,280 kWh a year at the main meter for 13,140 kWh measured at the UPS output has a PUE of 2: half the energy goes to cooling and losses. A PUE of 1 would be a room with no overhead at all.

How much does a 300 W server cost in electricity per year?

300 W drawn continuously is 2,628 kWh a year, or 657 € excl. VAT at 0.25 € excl. VAT per kWh. In a small room, which rarely gets below a PUE of 2, budget the same again for cooling and losses: 1,314 € excl. VAT a year per server.

What is the difference between kW and kVA for a rack?

kW is the power actually consumed, kVA the apparent power the supplier must deliver. The power factor links the two. IT power supplies with active correction sit around 0.98: five 300 W servers draw 1.5 kW, or 1.53 kVA. The two values are almost the same.

How long will a UPS last?

As a first approximation: battery bank voltage × capacity × depth of discharge × efficiency, divided by the load. Two 12 V 9 Ah batteries in series (24 V), discharged to 80% with 90% efficiency, give 155.5 Wh of usable energy, about 31 minutes at 300 W. Under heavy load, real runtime is shorter (Peukert's law): the manufacturer's curves prevail.

How many BTU/h must a server room remove?

All the energy IT consumes ends up as heat. 1 W equals 3.412 BTU/h: 1.5 kW of IT gives off about 5,118 BTU/h, i.e. 1.5 kW of cooling, plus lighting, people and outside heat gains.

Contact

Address

5 B RUE DES NOYERS, 95300 PONTOISE, FRANCE

Let's Talk About Your Project

15 minutes to understand your needs, no commitment.

Book a Slot